湖州ABB变频器维修,诸暨ABB变频器维修,杭州ABB变频器维修
湖州ABB变频器维修,诸暨ABB变频器维修,富阳ABB变频器维修
湖州ABB变频器维修,诸暨ABB变频器维修,富阳ABB变频器维修
杜国涛 先生( 业务经理)
地址:浙江杭州杭州市西湖科技园振华路206号西港新界B1幢606室
电话:86-0571-88301400
手机:13868198435
ABB变频器特价!abb变频器、买变频器、abb变频器价格、abb变频器报价\r\n(一)ACS510 IP21系列变频器\r\nACS510-01-03A3-4\r\nACS510-01-04A1-4\r\nACS510-01-05A6-4\r\nACS510-01-07A2-4\r\nACS510-01-09A4-4\r\nACS510-01-012A-4\r\nACS510-01-017A-4\r\nACS510-01-025A-4\r\nACS510-01-031A-4\r\nACS510-01-038A-4\r\nACS510-01-046A-4\r\nACS510-01-045A-4\r\nACS510-01-060A-4\r\nACS510-01-072A-4\r\nACS510-01-088A-4\r\nACS510-01-096A-4\r\nACS510-01-125A-4\r\nACS510-01-124A-4\r\nACS510-01-157A-4\r\nACS510-01-180A-4\r\nACS510-01-195A-4\r\nACS510 IP54系列变频器\r\nACS51...
ACS510-01-03A3-4+B055
ACS510-01-04A1-4+B055
ACS510-01-05A6-4+B055
ACS510-01-07A2-4+B055
ACS510-01-09A4-4+B055
ACS510-01-012A-4+B055
ACS510-01-017A-4+B055
ACS510-01-025A-4+B055
ACS510-01-031A-4+B055
ACS510-01-038A-4+B055
ACS510-01-045A-4+B055
ACS510-01-060A-4+B055
ACS510-01-072A-4+B055
ACS510-01-096A-4+B055
ACS510-01-124A-4+B055
ACS510-01-157A-4+B055
ACS510-01-180A-4+B055
ACS510-01-195A-4+B055
ABB变频器常见故障维修方法1、测试整流电路 找到变频器内部直流电源的P端和N端,将万用表调到电阻X10档,红表棒接到P,黑表棒分别依到R、S、T,正常时有几十欧的阻值,且基本平衡。相反将黑表棒接到P端,红表棒依次接到R、S、T,有一个接近于无穷大的阻值。将红表棒接到N端,重复以上步骤,都应得到相同结果。如果有以下结果,可以判定电路已出现异常,A.阻值三相不平衡,说明整流桥有故障。B.红表棒接P端时,电阻无穷大,可以断定整流桥故障或启动电阻出现故障。 2、测试逆变电路 将红表棒接到P端,黑表棒分别接U、V、W上,应该有几十欧的阻值,且各相阻值基本相同,反相应该为无穷大。将黑表棒N端,重复以上步骤应得到相同结果,否则可确定逆变模块有故障。动态测试 在表态测试结果正常以后,才可进行动态测试,即上电试机。在上电前后必须注意以下几点: 1、上电之前,须确认输入电压是否有误,将380V电源接入220VX变频器之中会出现炸机(炸电容、压敏电阻、模块等)。 2、检查变频器各接播口是否已正确连接,连接是否有松动,连接异常有时可能会导致变频器出现故障,严重时会出炸机等情况。 3、上电后检测故障显示内容,并初步断定故障及原因。 4、如未显示故障,X先检查参数是否有异常,并将参数复归后,在空载(不接电机)情况下启动变频器,并测试U、V、W三相输出电压值。如出现缺相、三相不平衡等情况,则模块或驱动板等有故障。 5、在输出电压正常(无缺相、三相平衡)的情况下,负载测试,尽量是满负载测试。
杜国涛 先生( 业务经理)
地址:浙江杭州杭州市西湖科技园振华路206号西港新界B1幢606室
电话:86-0571-88301400
手机:13868198435
湖州ABB变频器维修,诸暨ABB变频器维修,富阳ABB变频器维修
湖州ABB变频器维修,诸暨ABB变频器维修,富阳ABB变频器维修
湖州ABB变频器维修,诸暨ABB变频器维修,富阳ABB变频器维修